SECTION 07570
SWD Urethane Company
COATED
FOAM ROOF SYSTEM
Part 1 GENERALSUMMARY
Section Includes: Coated
foam roofing, as shown on drawings and specified herein.
1.01 SYSTEM DESCRIPTION:
a. One inch (minimum) of sprayed polyurethane foam
(additional inches may be added and /or sloped depending upon desired
insulation value) on the deck surface with (25) mil thickness of white,
reflective 100% acrylic roof coating with #9 white limestone granules or #11
ceramic granules imbedded into or on top of the wet coating at (30) pounds per
100 square feet. The roof system will provide a 10-year, no-leak warranty.
b. Low cost sustainable foam roof system is easily
maintained, repaired and upon inspection, may be re-coated with elastomeric
protective coating after ten (10) years.
1.02 SUBMTTTALS
1.03 QUALITY ASSURANCE
1.04 DELIVERY, STORAGE AND HANDLING
1.05 PROJECT/SITE CONDITIONS
1.06 WARRANTY
Part 2. PRODUCTS
2.01 MANUFACTURERS
2.02 MATERIALS
a. Primer /Sealer is not usually needed on new wood deck
b. Primer/Sealer is almost always needed on metal deck
and metal roof penetrations
Physical Properties
Property ASTM
Procedure Values
Core Density, pcf
nominal * D-
1622 2.5
- 3.0
Compressive Strength,
psi D-2621
40.1
Tensile Strength, psi
D-1623
85.5
Open Cell Content, % D-2856
17.7
Closed Cell Content %
D-2856
82.3
Water vapor
transmission, per/inch E-96
1.0
R Value C-
177 6.8
k-Factor (initial) C-
177 0.148
2. SWD 125 ÒQuik-ShieldÓ polyurethane foam is acceptable.
a. Polyurethane Foam Density and Compressive Strength
shall be uniform and consistent with specification. Minimum Physical Properties
shall not allow for multiple foam densities or compressive strengths to be
spray-applied within multiple inches of specified foam.
b. Polyurethane Foam shall contain EPA-approved 245fa
blowing agent and meet U.S. non-ozone depleting requirements of the U.S. EPA
mandate and International MontrealProtocol. No polyurethane foam with
phased-out HCFC 141b blowing agent is acceptable.
c. SWD Urethane Company, SWD 125 Polyurethane Foam with
HFC 245fa ÒEnovateÓ blowing agent is acceptable
Physical Properties
a. Property ASTM
Procedure Values
Fire Resistance E-84
Flame Spread E-84 15
Smoke Developed E-84 10
Solids Content
By Weight D-1353
70%
By Volume D-2697 60%
Solar Reflectance E-903 82%
Thermal Emittance E-408 91%
Solar Reflectance
Index, SRI E-1980 103%
Tensile Strength: psi D-412
280
Elongation psi D-412
355
Water Vapor
Transmission, ppi E-96 1
(Perms @ 20 mils)
Hardness
Hardness: Shore A
Durometer D-2240
60
Colors: Grey,
Buff, White
ASTM D-6083
– Standard Specificiation for Liquid-Applied Acrylic Coating
– Used in Roofing
(ALL FOLLOWING TESTS
PASSED)
Liquid
requirements/Film Properties:
Viscosity, Volume
Solids, Weight Solids, Initial Tensil Strength, Initial Elongation, Premeance,
Water Swelling, Wet Adhesion, Tear Resisitance, Fungi Resistance
Note: SWD Urethane
Company is an original "Energy Star" partner and approved by CRRC.
a. Dry film thickness shall be (25) mils application
with #9 limestone granules or #11 ceramic granules embedded at 3 0 Ibs per 100
square feet.
b. Base coat and top coat should be contrasting colors
to ensure adequate thickness and coverage.
c. SWD Urethane Company Quik-Shield ®ª 1929F
Acrylic Elastomeric Coatings are acceptable.
Part 3. EXECUTION
3.01 EXAMINATION
3.02 PREPARATION
a. All loose gravel, dust and residue shall be removed
using power-vacuum equipment, power-sweeper, air-blowing or other suitable
means. (Special conditions may be required if asbestos products are a part of
roof removal.)
b. The existing roof shall be thoroughly inspected for
adhesion between felts, insulation and deck. Areas of poor adhesion, if any,
should be fastened. Blisters, buckles, wrinkles and fish-mouths shall be cut
out and/or fastened.
c. Remove or re-fasten all loose base flashing,
counter-flashing and gravel-stops, as required.
a. The metal roof deck shall be constructed of minimum
22-gauge steel. Construction shall conform to local building codes.
b. Ferrous Metal: Sandblast iron and steel surfaces,
which are not primed, shop-painted, or otherwise protected. Remove loose rust
and primer from shop-primed iron and steel surfaces by scraping or wire
brushing.
c. Non-Ferrous Metal : Clean galvanized metal, aluminum
and stainless steel surfaces, as recommended by the manufacturer issuing the
warranty.
d. If the metal surface is free of loose scale, rust,
weathered or chalking paint, it can be cleaned using compressed air-jet, vacuum
equipment, hand or powerbroom to remove loose dirt. Grease, oil or other
contaminants shall be removed with proper cleaning solutions.
e. Fluted metal decks require a suitable method of
covering or filling the flute prior to polyurethane foam application. Flutes
may be covered with a suitable board stock, or quality (4) inch tape prior to
spray-application of the polyurethane foam. Where a fire barrier is required,
apply Type X gypsum board, mechanically-fastened to the metal surface, to meet
local building code requirements.
f. Metal flutes 2 3/4 inches up to (3) in width, may be
taped with 4" adhesive tape then sprayed with a minimum of 1 1/2 inches of
foam.
a. Remove loose dirt, dust and debris by using
compressed air, vacuum equipment or broom. Oil and grease from release agents
or other contaminants shall be removed with proper cleaning solutions.
b. All joint openings in concrete decks that exceed 1/4
inch shall be grouted or caulked by others, prior to application of polyurethane
foam.
c. Priming is required on concrete surfaces and it is
recommended that due to hydration usually present in new concrete, poured
concrete decks be permitted to cure for twenty-eight (28) days prior to the
application of sprayed polyurethane foam. Cutting time off of (4) weeks is not
a short cut SWD recommends.
d. Sprayed polyurethane foam is not recommended for
application over lightweight or insulating concrete materials unless
underlayment and/or vent pans are installed. (Check with manufacturer prior to
installation of PUF roof system over lightweight concrete).
a. Deck must meet building code requirements for
resistance to wind uplift.
b. Plywood shall contain no more than 18% water, as
measured in accordance with ASTM Standards. Plywood shall be exterior grade not
less than 1/2" thick, nailed firmly in place.
c. Plywood joints in excess of 1/4 inch, shall be taped
or filled by others with a suitable sealant material, prior to application of
polyurethane foam.
d. Deck shall be free of loose dirt, grease, oil or
other contaminants prior to priming or foam application. Remove loose dirt or
debris by use of compressed air, vacuum or broom. No washing shall be
permitted.
e. Tongue & Groove Sheathing or Planking: Due to the
frequency of joints, possibility
of variable openings and effects of aging and shrinking, these surfaces must be
overlaid with a minimum of 1/4 inch thick, exterior grade plywood or other
suitable covering with a minimum (1) inch thickness.
a. Such materials used over fluted metal decks must be
installed with mechanical fasteners or adhesives.
b. Fasteners shall be installed to meet UL or Factory
Mutual wind uplift criteria or the appropriate local building code criteria.
Note: ICC uses a ÒFactor of 2Ó to qualify ÒWind Uplift Resistance.Ó A UL Uplift
Resistance of 160 pcf equals 80 MPH.
c. Boards shall be firmly butted together along edges
without gaps or openings. Joints exceeding 1/4 inch shall be caulked by others
with a suitable sealant material.
d. Care shall be taken to prevent mineral or gypsum
board from getting wet in storage on the job-site and after installation, prior
to being protected by foam. Moisture exposure may damage these materials and
require replacement.
e. Remove loose dirt and debris by using compressed air,
vacuum or broom. No power-broom is permitted due to possibility of damage.
f. Installed materials shall be protected from spills,
contaminants, oil, grease and solvents, etc.
3.03 INSTALLATION -
GENERAL
a. Using 1/2 inch CDX plywood and structural lumber
adhered mechanical1y to the substrate and vertical walls installed by others.
b. Using spray polyurethane foam (within certain sloping
requirements).
c. Using tapered insulation board which shall be secured
to the substrate with an adhesive recommended by the tapered board manufacturer
or with mechanical fasteners.
3.O4 INSTALLATION –
PRIMER/SEALER
3.05 INSTALLATION -
POLYURETHANE FOAM
3.06 INSTALLATION -
PROTECTIVE ELASTOMERIC COATING
1. Foam surface and adjacent surfaces to be coated,
shall be dry and completely free of degraded foam, foam over-spray, grease,
oil, dirt or other contaminants which interfere with proper coating adhesion,
dry and free of contaminants.
2. Do not apply coating materials when surface
temperature is less than 50 degrees F.
3. Any physical damage to the polyurethane foam shall be
repaired before coating.
4. Operator should wear soft-soled shoes to avoid
damaging the skin of the foam.
5. An additional application of base coat shall be
applied where foam surface has been sanded, planed or trimmed.
B.
Application
1. Base Coat:
a. Shall be a contrasting color from the top coat to insure
adequate coverage.
b. Shall be applied on the same day, as the polyurethane
foam application, when possible.
c. The polyurethane foam shall be inspected for UV
oxidation if more than (72) hours has elapsed prior to application of base
coat.
d. Spray-apply elastomeric base coat over insulation at
the rate of (1) gallon per 100 square feet in one application.
2. Top Coat:
a. Coating shall be a contrasting color from the base coat to ensure adequate
coverage.
b. Do not apply top coat until base coat has cured
properly. Normally, 24 hours is sufficient time for the base coat to properly
cure.
c. Spray-apply acrylic elastomeric top coat over the
base coat at the rate of two gallons per 100 square feet in one application.
d. Coating passes shall be applied in cross-hatch
pattern at right angles to base coat passes to ensure more uniform coverage.
e. Coating shall extend up and over all polyurethane
foam on vent pipes, parapets and other penetrations and shall terminate a
minimum of (4) inches above the foam. All top coat termination points shall be
straight-lined on parapet walls, vent pipes and other penetrations for
effective use and uniform appearance.
3. Granules:
a. Granules when specified, shall be broadcast into or
on top of the wet top coating while it is being applied at the rate of 30
pounds per 100 square feet.
b. Shall consist of #11 ceramic granules or #9 limestone
granules.
3.07 CLEANING